In today’s society we are witnessing an electrification coupled with a surge in consumption of electricity. Consequently, there has been a notable increase of intergration of renewable energy sources, such as solar and wind power, onto the powergrid. Specifically, solar photovoltaic (PV) installations have experienced a substantial growth in recent years, predominantly among residential consumers, but also aslarger solar parks.
The operation of the Swedish power grid has, over the past decades, prioritizedfunctionality over further development of the grid. However, the significant rise inprivate solar PV installations present scenarios for which the grid was not initiallyequipped for. An example of this is the occurence of high voltages at residentialpremises when solar panels produces more electricity than the household consumes,resulting in reverse power flows.
The objective of this study has been to investigate the feasibility of dynamic voltageregulation through the implementation of a seasonally adjusted setpoint in the powertransformers of the 11 kV grid, aiming to mitigate overvoltage and undervoltage inthe low voltage grid. The studied network encompassed an area served by an existingtransformer station. To achieve this objective, the following questions were adressed:
1. What should be the appropriate setpoint seasonally for the tap changer toadjust the voltage of the secondary side of the medium voltage grid OLTC-transformer station 130 / 11 kV, in order to reduce the risk of overvoltage at 440 V without increasing the risk of undervoltage at 360 V?
2. How does the risk of overvoltage and undervoltage change by alternative mea-sures, such as consumption of reactive power in PV inverters or local ad-justment of the tap changers in the grid stations distribution transformers 11 / 0,42 kV?
Two case scenarios, consisting of two 11 kV grids and all of their repective 0,42 kV grids, were simulated using MATLAB to replicate segments of the grid, operated by the local utility company. The results indicated that reducing the setpoint by 1,67 % during the summer led to a decrease in the number of hours experiencing undesired overvoltage, without a significant increase in the likelihood of undervoltage. Further reduction of the setpoint by a total of 3,34 % eliminated all instances ofundesired overvoltage, but resulted in an increase in undesired undervoltage. Conversely, during the winter, increasing the setpoint resulted in undesired overvoltagein the network. Alternative measures, including reactive power consumption by PV inverters and local adjustment of tap changers, were analyzed in the most vulnerablelow voltage grid of the two case scenarios. Both measures eliminated all instancesof undesired voltage fluctuations during both summer and winter.
Based on the findings, it is concluded that during the summer, a reduction of thesetpoint by 1,67 % is advisable, while during the winter, no adjustment of the setpoint is recommended. However, it is important to note that the results should beconsidered indicitive and supportive of the proposed action, as only two of the ninefeeders in the grid were investigated. Furthermore, the results from alternative measures suggest the potential efficacy of more targeted interventions with less impacton the overall grid, compered to a seasonally adjusted setpoint.
2024. , p. 71