Systemanalys för ett optimalt fjärrkylsystem: Målkonflikter mellan kostnadseffektivitet och klimatpåverkan i Finspång
2026 (Swedish)Independent thesis Advanced level (degree of Master (Two Years)), 20 credits / 30 HE credits
Student thesisAlternative title
System Analysis for an Optimal District Cooling System : Trade-offs between Cost-Effectiveness and Climate Impact in Finspång (English)
Abstract [sv]
I takt med att klimatförändringar leder till högre temperaturer ökar behovet av komfortkyla, vilket ställer krav på effektiva och hållbara fjärrkylsystem. De vanligaste kylteknikerna i fjärrkylsystem i Sverige är kompressorkylmaskiner, absorptionskylmaskiner och frikyla, varav de två sistnämnda finns i Finspångs fjärrkylsystem. Studien syftar till att utvärdera prestandan i fjärrkylsystemet i Finspång samt optimera systemet genom val av kylteknik och effektdimension för att minimera totala systemkostnader respektive klimatpåverkan. Utvärderingen av det befintliga systemet (Sc0) baserades på timvisa driftdata från 2020. Därefter genomfördes systemoptimeringar i MATLAB med blandad linjär heltalsoptimering (MILP) utifrån två perspektiv: minimering av total årskostnad respektive minimering av klimatpåverkan. Dessa perspektiv tillämpades på två scenarier: ett bestående av enbart kompressor- och absorptionskylmaskiner, samt ett där även en ackumulatortank inkluderades, vilket resulterade i totalt fyra olika scenarier (Sc1, Sc2 Sc3 och Sc4). För att säkerställa redundans ställdes krav på minst två kylmaskiner i samtliga scenarier. Slutligen utvärderades hur de två scenarierna, innehållande både kylmaskiner och en ackumulatortank, påverkades av förändrade energipriser, emissionsfaktorer och kyllast, samt systemets redundans vid driftstopp.
Analysen av det befintliga systemet visar på låg energieffektivitet med lägre COP-värden för absorptionskylmaskinen (COPvärme 0,4) och frikylan (COPel 2,1) än referensvärden för respektive teknik. Vidare är den befintliga absorptionskylmaskinen överdimensionerad och nyttjar i genomsnitt 11 procent och maximalt 67 procent av kapaciteten. Dessutom styrs distributionspumparna i systemet inte efter kundernas kylbehov och flödet höjs vid tidpunkter då kylbehovet är lågt, exempelvis nattetid. Det medför att energianvändningen ökar utan att någon kyla levereras.
Optimeringsresultaten påvisar en tydlig målkonflikt mellan att minimera systemets kostnader och dess klimatpåverkan. För att nå en kostnadsoptimal utformning (Sc1) bör fjärrkylsystemet bestå av två kompressorkylmaskiner på 172 kW respektive 271 kW. För en klimatoptimal lösning (Sc4) bör systemet istället vara mer diversifierat, bestående av en absorptionskylmaskin på 316 kW och en kompressorkylmaskin på 172 kW kompletterat med en ackumulatortank. Implementeringen av en ackumulatortank visar sig vara en avgörande komponent för systemets prestanda och redundans. Genom möjligheten till lastförskjutning kunde ackumulatortanken sänka driftkostnaderna med upp till 60 procent i det kostnadsoptimala scenariot (Sc3) och minska klimatpåverkan under drift med 75 procent i det klimatoptimala scenariot (Sc4) jämfört med nuläget.
Känslighetsanalyserna visar att systemen som inkluderar en ackumulatortank har en hög resiliens. Varken en ökning av elspotpriset med 50 procent eller en minskning av pelletspriset med 66 procent ledde till ett skifte av kylteknik, och prisförändringarna påverkade enbart systemets totalkostnad med 2 procent. Förändrade emissionsfaktorer i elsystemet sänkte den årliga klimatpåverkan med 41 procent men ledde inte heller till något kylteknikskifte.
Slutligen fyller ackumulatortanken en viktig funktion för systemets redundans. Vid en fördubbling av kyllasten underlättar tanken expansionen genom att kapa de högsta effekttopparna och även behovet av installerad kylkapacitet (Sc3), även om investeringar i större maskiner krävs. Vid ett simulerat driftstopp av den mindre kompressorkylmaskinen ger tanken systemet full redundans så att hela kylbehovet kan täckas under årets varmaste vecka. Skulle den större kylmaskinen tas ur drift uppstår enbart ett kylunderskott under 8 procent av topplastveckans timmar.
Abstract [en]
As climate change leads to rising temperatures, the demand for comfort cooling increases, placing higher requirements on efficient and sustainable district cooling systems. The most common cooling technologies in Swedish district cooling systems are compression chillers, absorption chillers, and free cooling, the latter two of which are currently utilized in Finspång's district cooling system. This study aims to evaluate the performance of the district cooling system in Finspång and optimize it through technology selection and capacity dimensioning to minimize total system costs and climate impact, respectively. The evaluation of the existing system (Sc0) was based on hourly operational data from 2020. Subsequently, system optimizations were performed in MATLAB using Mixed-Integer Linear Programming (MILP) based on two objectives: minimization of total annual cost and minimization of climate impact. These objectives were applied to two configurations: one consisting only of compression and absorption chillers, and one including a thermal energy storage (TES) tank, resulting in a total of four scenarios (Sc1, Sc2, Sc3 och Sc4). To ensure redundancy, a requirement of at least two chillers was set for all scenarios. Finally, the resilience of the scenarios containing both chillers and a TES tank was evaluated against changes in energy prices, emission factors, and cooling loads, as well as system redundancy during operational outages.
The analysis of the existing system indicates low energy efficiency, with lower Coefficient of Performance (COP) values for the absorption chiller (COPheat 0,4) and free cooling (COPel 2,1) than the reference values for each technology. Furthermore, the existing absorption chiller is significantly oversized, utilizing on average 11 percent and at most 67 percent of its capacity. Additionally, the distribution pumps are not controlled according to actual customer cooling demand where flow rates increase when demand is low, such as at night. This results in increased energy consumption without corresponding cooling delivery.
Optimization results demonstrate a clear trade-off between minimizing system costs and climate impact. To achieve a cost-optimal design (Sc1), the district cooling system should consist of two compression chillers of 172 kW and 271 kW, respectively. For a climate-optimal solution (Sc4), the system should instead be more diversified, consisting of a 316 kW absorption chiller and a 172 kW compression chiller supplemented by a TES tank. The implementation of a TES tank proves to be a decisive component for system performance and redundancy. By enabling load shifting, the tank was able to reduce operational costs by up to 60 percent in the cost-optimal scenario (Sc3) and reduce the climate impact during operation by 75 percent in the climate-optimal scenario (Sc4) compared to the current state.
Sensitivity analyses show that systems including a TES tank exhibit high resilience. Neither a 50 percent increase in the electricity spot price nor a 66 percent decrease in the pellet price led to a shift in cooling technology, and price fluctuations only affected the total system cost by 2 percent. Changing emission factors in the power system lowered the annual climate impact by 41 percent but did not trigger a change in technology selection.
Finally, the TES tank fulfills a critical function for system redundancy. In the event of a doubling of the cooling load, the tank facilitates expansion by shaving the highest peak loads and the need for installed cooling capacity (Sc3), although investments in larger machines remain necessary. During a simulated outage of the smaller compression chiller, the tank provides full redundancy, allowing the entire cooling demand to be met during the warmest week of the year. If the larger chiller were taken out of service, a cooling deficit would occur during only 8 percent of the hours in the peak-load week.
Place, publisher, year, edition, pages
2026. , p. 68
National Category
Energy Systems
Identifiers
URN: urn:nbn:se:liu:diva-225084ISRN: LIU-IEI-TEK-A--26/05324--SEOAI: oai:DiVA.org:liu-225084DiVA, id: diva2:2073619
External cooperation
Finspångs Tekniska Verk
Subject / course
Energy Systems
Supervisors